Verso
Installation manual
Last updating 05 of July 2024
INTRO
The VERSO universal transmitter is a module that allows you to associate a third-party sensor (NC/NO) within the D’AVINCI system. It transmits alarm signals, intrusion, fire, SOS, gas, flooding, etc. Provides a 3.3 V supply voltage to the sensor with two input terminals for alarm and tampering.The device for its own protection and equipped with an accelerometer that protects it from tampering.
OPERATION
VERSO works within the D’AVINCI system with a range of up to 1500 meters (in free space) by connecting, via radio, directly to the Lisa control panel or via Automa repeater. The communication is bidirectional (transmission/reception) with the indication of confirmation of receipt and command. In the case of obstacles such as walls, objects, etc. the range is reduced.
The communication protocol, like the connections between all the components of the system, is the GENIO, encrypted and protected from interception.
Configuration takes place via D’AVINCI app downloadable for free from IOS and Android.
The transmitter operates on two frequencies in the 868 MHz band, automatically and dynamically positioned on the one that is free or less interfered.
DEVICE CONFIGURATION IN THE D’AVINCI SYSTEM
Warning. Before adding the device:
- Install the D’AVINCI app, available for iOS/Android, on your smartphone.
- Create an account. Add a D’AVINCI Control Panel, save the necessary settings and create at least one Room
- Make sure the Control Panel is on and has internet access via Ethernet cable.
- Make sure that the Control Panel is off and not running updates by checking its status via the mobile application.
To add a device to the Control Panel, in the D’AVINCI app 1
- Select the tab Device 2
- Click on Add Device
- Assign a name to the device
- Insert the serial number of the device shown on the label or click on icon to scan the code via the app.
- Select the associated Room for the device.
- Click Add. – a countdown will start
- Turn on the device via the ON/OFF button .The Transmitter connected to the Control Panel will appear in the list of Devices in the D’AVINCI app.The connection request to the Control Panel is transmitted for a short period of time as soon as the device is switched on.
If the connection to the D’AVINCI control panel fails, turn off the detector for 5 seconds and repeat the procedure.
1 Installer privileges are required
2The device must be located within the radio communication zone of the associated Control Panel in order to start the configuration procedure.
TRANSMITTER INSTALLATION
The Verso transmitter must be installed inside the body of a third-party detector. The board needs a minimum space of the following dimensions: 40 x 95 x 20 mm.
Connect the transmitter to the detector via the NC/NA contacts.
FUNCTION OF TERMINAL BOXES:
- TAMPER | Tamper terminal
- ALARM | Alarm Terminal
- +OUT- | Power supply terminal (3,3 V DC)
Fix the device inside the sensor box (if availabe)
We recommend installing Verso using adhesive media.
Insert the 3 batteries on the transmitter
Press the ON/OFF power button
Do not install the transmitter:
- Near metal objects or mirrors that may attenuate or block the radio signal.
- Next to other radio devices (gsm/wireless router/etc.) to avoid mutual interference
- In environments where temperature or humidity values may exceed the limits specified in the Technical Specifications.
Operating settings
The detector settings can be changed in the D’AVINCI app:
- Navigate to Devices
- Select the device from the list.
- Go to settings by clicking on the icon
DEVICE NAME
Transmitter name , displayed in the device list and as notification text.
Can hold up to 24 characters
ROOM
Selecting the virtual room to which the device is assigned
The environment name appears in notifications.
*Changing this parameter requires Administrator privileges
ALARM MODE
Shows how the device reacts to alarms.
– Instantaneous: the detector, with the system inserted, immediately signals the alarm
– Delayed: the detector, with the system inserted, signals the alarm after a time counter (see input/ output delay).
– Input delay: 5 to 120 seconds.
The entry delay is the time the user has to disconnect the system after entering the protected area.
– Output delay: 5 to 120 seconds.
The exit delay is the time the user has to leave the protected area after entering.
– Continued: The detector adds input/output delays of devices that detected an alarm before it. When activated individually, it immediately triggers the alarm
ARMING STAY MODE
Pairing the detector or associated device to night mode. This type of insertion allows, for example, to insert the perimeter area and allows people to move freely in other areas.
– Input delay in stay mode: 5 to 120 seconds.
The entry delay is the time the user has to disconnect the system after entering the protected area.
– Output delay in stay mode: 5 to 120 seconds.
The exit delay is the time the user has to leave the protected area after entering.
ALWAYS ACTIVE
If this option is enabled, the detector associated is always armed, detects the alarm condition and sends the signal to the control panel.
POWER OUTPUT MODE
Enables/disables the 3.3 power output for the associated detector
– Always enabled
– Enabled on insertion
– Always disabled
EXTERNAL INPUT USAGE
Enables/disables the use of external input
– External contact mode:
– normally open
– normally closed
– External detector type:
– bistable
– impulsive
USE TAMPER STATE INPUT
Enables/disables the use of the tamper contact
DISPLACEMENT SENSOR USAGE
Allows you to enable/disable the use of built-in acceleration to signal an alarm if the device moves.
ALARM TYPE
Sets the alarm type of the detector or connected device.
– Intrusion
– Fire
– Rescue
– Anti-panic
– Gas leak alarm
– Breakdown
– Flooding
– Other
ACTIVATE SIREN FOR EXTERNAL INPUT
When an alarm occurs, the siren goes on.
SIREN ON A TAMPER
The moment the device is tampered with, the siren is activated.
ACTIVATE SIREN FOR DISPLACEMENT SENSOR
The siren is activated when the transmitter is moved.
SELF-EXCLUSION ALARMS
Allows you to enter the number of alarms for the detector associated, during the same insertion, which cause the automatic exclusion of the detector associated.
The detector will be automatically included the next time the system is armed.
– Disabled
– 3 , 6, 9, 12 , 15.
WARNING LIGHT
Enables the light indication for the alarm signal.
– only test operation
– always
REPEATER USAGE
Enables the connection of to the system through a repeater, eg Automa.
Repeater number: Indicates the number the detector is associated with.
VERIFY RADIO CONNECTION
Enables alarm signaling in case of failure to communicate with the control panel.
If disabled, the report of failure to connect to the control panel will be stored exclusively.
– ping interval: time interval, in seconds, between one survival transmission and the next in the absence of activation.
– [ 12 : 600 ] seconds
– Number of ping: number of connection attempts before radio failure report
– [ 1 :15 ]
RADIO SIGNAL INTENSITY TEST
With this function, the device after pressing the START button processes a test where it will indicate the signal level, flashing n times depending on the result obtained.(1-4)
EXCLUDE DEVICE
With this function, it can be excluded only the tampering or in total mode , so as to be completely excluded from operation with the power plant, not signaling alarms or events.
REMOVE DEVICE
Dissociate the transmitter from the Control Panel, removing it from the app and deleting the device settings.
iNTENSITY GENIO SIGNAL
The level of the radio signal GENIO is determined by the number of packets sent by the transmitter and the actual number of packets received by the associated control panel.
To view the signal strength select the Devices and the signal level field GENIO
0 = no radio signal, no connection to the Control Panel.
• = poor radio signal, unstable connection to the Control Panel , operation of the transmitter not guaranteed.
• • = low radio signal, low signal strength.
• • • = good radio signal, good signal strength.
DEVICE STATUS
The status shows information and parameters of operation of the transmitter
To view the status:
- Access the D’AVINCI application
- Select the Control Panel on which the transmitter is associated
- Go to Devices tab
- Select the transmitter
Icon | Description | Note |
Connection status | - Online : connection established with the control panel
- Offline : connection error with the control panel |
|
Genio Level Signal | - 0
- 1 - 2 - 3 - 4 | |
Battery level |
- 25 %
- 50 % - 75 % - 100 % | |
Tampering status | - Alarm
- Regular | |
Primary input state | - Regular
- Alarm | |
Warning status if moved | - Adjust
- Alarm | |
Device exclusion status | - No
- Total - Only tampering |
|
Always active | - No
- Yes | |
Alarm mode | - Instant
- Delayed - Continued | |
Arming in Stay mode | - No
- Yes | |
Repeater usage | - No
- Yes (1-5) | |
REPLACING BATTERIES
Keep the transmitter housing clean by immediately removing dust, cobwebs and other impurities. Use a soft, dry towel for equipment maintenance.
To clean the transmitter, avoid the use of substances containing alcohol, acetone, gasoline or other active solvents.
The life of the transmitter batteries depends on their quality and on the frequency of activation of the detector and the ping interval between the detector and the panel control.
If the transmitter batteries are low, the user receives a notification via D’AVINCI app.
WARNING AND MALFUNCTIONS
The warning and malfunction indication feature is enabled in the device settings by selecting the Warning light
Indication | Event |
LED red flashes | Alarm confirmation/tampering |
Red LED 3 flashes on power | Inserted flat battery |
- Transmitter batteries are low.[/et_pb_text]
TECHNICAL SPECIFICATIONS
Type of sensor | Wireless universal transmitter |
Type | Alarm terminal block,tamper(NA/NC) |
Mode of detection signals | Impulsive/Bistable |
Inhibition time | Programmable from the control panel |
Radio communication protocol | Genio |
Operating frequencies | 868.20 Mhz 868.95 Mhz |
Rf signal power | 13 dB |
Modulation | GFSK |
Radio signal range | Up to 1500 m |
Power supply | 3 batteries CR123A - 3V |
Device power supply capacity | 3.3 V DC - 100ma |
Ping interval | 12 - 300 seconds |
Anti-sabotage | Device MEMS accelerometer(excluded) |
Battery life | 5 years |
Installation | Indoor |
Class of protection | IP20 |
Operating temperatures | From -15 ºC to +55 ºC |
Maximum permissible humidity | Up to75% |
Dimensions | 96x39x24 mm |
Weight | 70 grams |
Copyright 2023 - 2024 – D’AVINCI Security Products Srl – C.F. e P.IVA 12908830966 – All right reserved. || privacy policy